EATON POWERWARE 93PM
Your problem, our solution
The Eaton 93PM UPS is not just one solution - it's many.
Our Large Systems Group can work with you and with our local sales and project management teams, to create a solution tailor-made for your large data centre, providing high power performance, maximum availability and cost-efficient operation, with a minimum TCO.
TAke complete control
Managing and controlling your Eaton 93PM UPS is easy. Designed for the most advanced IT environments, the 93PM comes equipped with intuitive user interfaces, a large touchscreeb LCD providing useful status information and back logs, and a full suite of power management and connectivity options.
Eaton® 93PM UPS 30–200 kW
Maximum energy efficiency Minimum operating costs
The Eaton 93PM UPS features market-leading operating efficiency and world-class intelligent software solutions, to ensure the continuity of your mission-critical operations with a minimum TCO.
The market-leading advantage in sustainability, efficiency and TCO
The Eaton 93PM UPS leads the market for sustainability and efficiency. High operating efficiency in double conversion is achieved with high-end converter technology. In addition, an innovative Energy Saving System (ESS) technology enables reaching > 99% energy efficiency with double conversion available on-demand. Together they enable achieving a better PUE in data centres, helping to bring down the Total Cost of Ownership.
Grow your system, increase availability, reduce your CapEx
The modular design of the Eaton 93PM UPS makes it simple and cost-effective to scale your system as your load demands change. At the same time, centralised topology, patented Hot Sync® wireless paralleling, and service-friendly design feaures help to ensure increased availability. And ultimately, the Eaton 93PM UPS helps to minimise your CapEx as well as Total Cost of Ownership.
TECHNICAL SPECIFICATIONS
| General | |
|---|---|
| UPS output power rating(1.0 p.f .) | 30, 40, 50, 80, 100, 120, 150, 160, 200kW |
| Efficiency in double conversion mode | Up to 97% |
| Efficiency in Energy Saver System(ESS) | > 99% |
| Static bypass rating | Yes |
| inverter/rectifier topology | Transformer-fee IGBT with PWM |
| Audible noise | 30–50 kW: < 60 dBA 80–200 kW: < 65 dBA ESS operation : < 47 dBA |
| Altitude(max) | 1000m without deration(max 2000m) |
| Input | |
| InputInput wiring | 3ph + N + PE |
| Nominal voltage rating(configurable) | 220/380, 230/400, 240/415 V 50/60 Hz |
| Input voltage range | High, +20% rectifier Input, 10% bypass Input Low, -15% at 100% load, 40% at 50% load without Battery discharge |
| Input frequency range | 40–72 Hz |
| Input power factor | 0.99 |
| Input ITHD | 30 kW: < 4.5% 40–200 kW: < 3% |
| Soft start capability | Yes |
| internal backfeed protection | Yes |
| Battery | |
| Battery Type | VRLA |
| Charging method | ABM technology or Float |
| Temperature compersation | Optional |
| Battery nominal voltage(VRLA) | 432 V (36 x 12 V, 216 cells) or 480 V (40 x 12 V, 240 cells) note : Strings with differrent battery voltage may nt be paralleled |
| Charging current maximum | 30–50 kW: 16.5A 80–100 kW: 33A 120–150 kW: 49.5A 160–200 kW: 66A |
| Battery startcapability | Yes |
| Output | |
| OutputOutput wiring | 3ph + N + PE |
| Nominal voltage rating(configurable) | 220/380, 230/400, 240/415 V 50/60 Hz |
| Output UTHD | < 1% (100% linear load). < 5% (criteria non-linear load) |
| Rated output power factor | 1.0 |
| Permitted load power factor | 0.8 lagging - 0.8 leading |
| Overload on inverter | 10 min 102–110%; 60 sec 111–125%; 10 sec 126–150% 300 ms > 150% . On battery mode 300 ms > 126% |
| Overload when bypass available | Continuous < 125%, 10ms 1000% Note : bypass fuses may limit the overload capability |
| Accessories | |
| External battery cabinet with long-life batteries, External maintenance bypass switch, intergratied manual bypass, MiniSlot connectivityd(Web/SNMP, ModBus/Jbus, Relay) |
|
| Communications | |
| MiniSlot | 3 communications bays |
| Network/SNMP interface | Yes, Standard |
| Serial ports | Buit-in host and device USB |
| Relay Input/Output | 5 relay Inputs and docicated EPO 1 relay Output |
| Compliance with standards | |
| Safety(CB certified) | IEC 62040-1 |
| EMC | IEC 62040-2 |
| Performance | IEC 62040-3 |