EATON POWERWARE 9395P
Key apllications
• Large datea centers
• Colocation facilities
• Server farms
• Telecommunication installations
• Internet service providers
• Transportation systems
• Security operations
• Broadcasting and entertainment
• Process control eqiopment
• Financial systems
• Credit card operations
• Healthcare
• Industrial systems
• Multiple medical imaging units
Leading sustainability
• Highest efficiency ratings lower utility costs
• Lowest total cost of ownership and lifecycle carbon footprint
• Smallest footprint and weight
• Lowest transportation and installation costs
Stronger power performance
• Lowest input to THD enhance compatibility with upstream power systems
• Lowest output THD
• Optimum generator sizing
• PFC power supply compatible
Highest relability and availability
• Powerware Hot Sync wireless parallenling
• Superior battery management
• Inherent redundancy
• Scalable architecture that adpts to increasing power requirements
Robust manageability
• superior control and connectivity
• 10-inch color touchscreen display provides metering and management options
Introduction and overview
For more than 40years, Eaton has been dedicated to delivering the most technologically advanced products for our customers'mission-critical applications - a commitment exemplified by the Power Xpert™ 9395 UPS. With an unprecedented level of power performance, reliability and energy savings, the state-of-the-art 9395 has raised the bar in three-phase power protection technology.
The 9395 delivers a wide scope of superior customer-driven benefits unmatched by competitive UPS solutions, including:
Measuring power performance: efficiency, power factor and THD
Power poerformance, which is measured by system efficiency, output power factor and THD, is the foundation of the 9395. It's the UPS's robust combination of these three elements that make it stand out as the premier UPS in its class. The table below demonstrates how the 9395 with Energy Saver System (ESS) compares to competitive UPS models. Most manufacturers must use input filters, which lower their efficiency rating, but the 9395 doesn't require them to obtain excellent input THD.
The reliable solution
Providing high availability for your critical systems at all times, the 9395 was designed with numerous technological advancements that create an unprecedented level of reliability while emphasizing serviceability-lowering MTTR and enhancing availability.
Double-conversion design offers the highest protection possible
Unlike some other commercially available UPS technologies, the double-conversion design completely isolates output power from all input power anomalies and delivers 100-percent conditioned, perfect sine-wave output - regulating both voltage and fequency. Even when presented with the most severe power disturbances, power output remains stable. Output voltage THD is held within two percent for nonlinear loads - making the 9395 ideal for supporting equipment that's sensitive to a distorted voltage input. Additionally, the 9395 excels at supporting leading power factor loads, which becoming more prevalent in new or updated data centers. The 9395 handles leading loads, down to 0.9 power factor, without de-rating.
Inherent redundancy option
Surveys focused on efficiency in data centers revel that UPSs are often under-loaded-frequently at less than 50 percent. To capitalize on this trend and create even greater reliability, you have the option to configure the 9395 with inherent redundancy. Traditional UPS manufacturers can't deliver this additional availability without adding a more costly second UPS module.
TECHNICAL SPECIFICATIONS
| UPS output power rating | ||
|---|---|---|
| kVA | 250 275 300 400 500 550 600 750 825 900 1100 1200 | |
| kW | 250 275 275 400 500 550 550 750 825 825 1100 1100 | |
| General | ||
| Efficiency in double conversion mode | Up to 96.5% | |
| VMMS(double conversion) | Significantly increased eficiency at low loads | |
| Efficiency in Energy Saver System(ESS) | Up to 99.3% | |
| Distributed parallenlling with Hot Sync technology | Up to 8 | |
| Internal N+1 redundance capable | in 600 kVA : 300kVA in 900 kVA : 600kVA in 1100 kVA : 900kVA |
|
| Field upgradable | Yes | |
| Inverter/rectifier topology | Transformer-free IGBT with PWM | |
| Audible noise-Typical | < 75dB | |
| Continuous Maximum Operation Temperature | 40℃ | |
| Altitude(max) | 1000m without deration(max 2000m) | |
| Input | ||
| Input wiring | 3 ph + N + PE | |
| Nominal voltage rating(configurable) | 220/380, 230/400, 240/415 V 50/60 Hz | |
| Input voltage range | -15% / +15% | |
| Input frequency range | 45 ~ 65 Hz | |
| Input power factor | 0.99 | |
| Input ITHD | < 3% on nominal load in double conversion mode | |
| Soft start capability | Yes | |
| Output | ||
| Output wiring | 3ph + N + PE | |
| Nominal voltage rating(configurable) | 220/380, 230/400, 240/415 V 50/60 Hz | |
| Output UTHD | < 2%(100% linear load) | |
| Output power factor | 0,9(300, 600, 900 and 1200kVA models) 1.0(other models) |
|
| Permitted load power factor | 0,7 lagging ~ 0,8 leading | |
| Overload on inverter | 10min 100 ~ 110%, 30sec 110 ~ 125%; 10sec 125 ~ 150%, 300ms > 150% |
|
| Overload when bypass available | Continuous < 115%, 20ms 1000% Note, bypass fuses may limit the overload capability |
|
| Battery | ||
| Type | VRLA, AGM, Gel, Wet Cell | |
| Charging method | Current limited constart voltage charging, Eaton Advanced Battery Management(ABM) |
|
| Temperature compersation | Optional | |
| Battery nominal voltage(lead-acid) | 480 V(40 x 12 V, 240 cells) | |
| Charging current/Model Max* A |
120A per UPM | |
| * Limited by maximum UPS input current rating | ||
| Dimensions and weights | ||
| 300 kVA | 1350 x 880 x 1880mm(w x d x h) | 830 kg |
| 600 kVA | 1890 x 880 x 1880mm(w x d x h) | 1440 kg |
| 900 kVA | 3590 x 880 x 1880mm(w x d x h) | 2680 kg |
| 1100 kVA | 4350 x 880 x 1880mm(w x d x h) | 3120 kg |
| Accessories | ||
| UPM Service Disconnet | Optional | |
| Internal Backfeed | Optional | |
| 7"/10" Touch Screen | Optional | |
| X-Slot connectivity(Web/SNMP, ModBus/Jbus |
Relay, Hot Sync, View UPS-X remote display),
integrated manual bypass for 300kVA model
||
| Communications | ||
| X-Slot | 4 communication bays | |
| Relay inputs/outputs | 5/1 programmable | Compliance with standards |
| Safety(CB certified) | IEC 62040-1 | |
| EMC | IEC 62040-2 | |
| Performance | IEC 62040-3 | |